Tekmar 275 Boiler Control Manual do Utilizador Página 31

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 48
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 30
31 of 48 © 2012 275_D - 11/12
Item Field Range
Access
Description
VIEW
2
0 to 100 %
or
1 to 4
ADV
BOILER 2 MODULATION / STG
SECTION D
Current percent modulation of the boiler 2 burner.
If the BTC I / Off DIP is set to BTC I, the BTC I
number of stages is displayed.
Note: This item is only available when boiler 2 is
set to Auto or CP1.
VIEW
3
0 to 100%
or
1 to 4
ADV
BOILER 3 MODULATION / STG SECTION D
Current percent modulation of the boiler 3 burner. If
the BTC I / Off DIP is set to BTC I, the BTC I number
of stages is displayed.
Note: This item is only available when boiler 3 is set
to Auto or CP1.
VIEW
4
0 to 100%
or
1 to 4
ADV
BOILER 4 MODULATION / STG SECTION D
Current percent modulation of the boiler 4 burner. If
the BTC I / Off DIP is set to BTC I, the BTC I number
of stages is displayed.
Note: This item is only available when boiler 4 is set
to Auto or CP1.
VIEW
1
hr
0 to 9999 hours
ADV
BOILER 1 RUNNING TIME SECTION C
The total running time of boiler 1 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This
item is only available when boiler 1 is set to Auto.
VIEW
2
hr
0 to 9999 hours
ADV
BOILER 2 RUNNING TIME SECTION C
The total running time of boiler 2 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This item
is only available when boiler 2 is set to Auto or CP1.
VIEW
3
hr
0 to 9999 hours
ADV
BOILER 3 RUNNING TIME SECTION C
The total running time of boiler 3 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This item
is only available when boiler 3 is set to Auto or CP1.
VIEW
4
hr
0 to 9999 hours
ADV
BOILER 4 RUNNING TIME SECTION C
The total running time of boiler 4 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This item
is only available when boiler 4 is set to Auto or CP1.
VIEW
hr
Primary
1
0 to 9999 hours
ADV
PRIMARY PUMP 1 RUNNING TIME SECTION L
The total running time of pump 1 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item.
VIEW
hr
Primary
2
0 to 9999 hours
ADV
PUMP 2 RUNNING TIME SECTION L
The total running time of pump 2 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item.
Note: This item is only available when the Pump
Sequencer / Off DIP Switch is set to Pump
Sequencer.
After the last item, the control returns to the first item in the menu.
View Menu (2 of 2)
VIEW MENU