25 of 36
Copyright © D 362 - 12/08
362 Adjust Menu (4 of 4)
Actual
Setting
The maximum length of time that the mixing pump
continues to operate after the mix demand
is removed.
OFF, 0:10 to 40:00 min
Default = 0:20 min
Enables or disables the Soft Start feature in
the control.
MODE = —1—
NONE, MIX
Default = NONE
The frequency with which the control exercises the
pumps and valves that are operated by the control.
30 to 240 hr, OFF
Default = 70 hr
Section
LTD
INST
ADV
Range
Access
Level
DescriptionItem Field
USER
B1
C1
B1
A
The type of setback override that is in effect for
the heating system.
DIP switch =
Setback
MODE = —1—
AWAY is available even if DIP ≠ Setback
NONE, TMPY Occ Ovr, PERM
Occ Ovr, TMPY UnOcc Ovr,
PERM UnOcc Ovr, AWAY Ovr
Default =NONE
The override that is in effect for the snow melting
system.
MODE = —2—
NONE, AWAY
Default =NONE
362 Schd (Schedule) Menu (1 of 1)
Section
LTD
INST
ADV
Range
Access
Level
DescriptionItem Field
USER
B1
C1
˚F, ˚C
Default = °F
The units of measure that all of the temperatures are to be
displayed in by the control.
362 Misc (Miscellaneous) Menu (1 of 2)
LTD
INST
ADV
Range
Access
Level
DescriptionItem Field
USER
362 Monitor Menu (see pages 30 - 32)