Tekmar 364 Universal Reset Control Installation Manual do Utilizador Página 1

Consulte online ou descarregue Manual do Utilizador para Sensores Tekmar 364 Universal Reset Control Installation. tekmar 364 Universal Reset Control Installation User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 36
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
- Data Brochure
Universal Reset Control 364
D 364
07/01
1 of 36 © 2001 D 364 - 07/01
The Universal Reset Control 364 is designed to maximize the comfort and efficiency provided by a hydronic heating system. The
control automatically adjusts the boiler and mixed loop water temperatures that are delivered to the heating system by using outdoor
reset. For a mixing device, the 364 can use either a variable speed injection pump or a floating action mixing valve. The mixed water
temperature can be used to supply either a space heating system or a single zone snow melting system. The 364 is capable of
controlling an indirect Domestic Hot Water (DHW) storage tank and / or a setpoint load. The temperature of individual zones can be
controlled by connecting either a conventional thermostat system or a tekmar zone control to the 364. A large Liquid Crystal Display
(LCD) is incorporated in order to view system status and operating information.
Warm Weather Shut Down (WWSD)
Manual Override
Optional DHW Priority
Remote Display and Adjustment Capabilities
Test Sequence to Ensure Proper Component Operation
120 V (ac) Power Supply
CSA C US Certified (approved to applicable UL standards)
Additional features include:
Do not apply power
1
Mix
Demand
2 3
Boil
Dem
4
Com
Dem
5
Setp/
DHW
6
Power
N
7
L
8
Prim
P1
9
Boil Sys
Pmp P2
Mix Sys
Pmp P3
DHW
Pmp/Vlv
10 11 12 13 14 15
Boiler
16 17
Pwr
Mix
18
Opn
19
Cls/
Var
20
Com
21
Mix
10K
22
Mix
Ret
23
Mix
Sup
24
Com
25
Boil
Zo In
26
Boil
27
Com
28
DHW
29
Out
30
tN2
Mix Demand
Boiler Demand
DHW Demand
Setpoint Demand
WWSD
Min / Max
Melting
Universal Reset Control 364
Mixing, Boiler & DHW
158033
Snow Melting
Mixing Reset
Made in Canada by
tekmar Control Systems Ltd.
tektra 928-01
For maximum heat,
press and hold Test
button for 3 seconds.
not testing
testing
testing paused
off
red
red
Signal wiring must be rated at least 300 V.
Power 120 V ± 10% 50/60 Hz 1300 VA
Relays 240 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Var. Pump 240 V (ac) 2.4 A 1/6 hp, fuse T2.5 A 250 V
Demands 20 to 260 V (ac) 2 VA
Menu Item
Test
Input
Universal Sensor
Optional
Input
tekmar Zone Control,
Slab Sensor, or Indoor Sensor
for mixing zones
Output
Mixing Valve &
Actuating Motor
Output
Var. Speed
Driven Pump
Output
Boiler
Output
DHW Pump
OR
DHW Valve
Output
Boiler
System
Pump
Output
Primary
Pump
Output
Mixing
System
Pump
M
M
Input
120 V (ac)
Power
Supply
Input
Outdoor
Sensor
Included
Input
Universal Sensor
Included
Input
Universal Sensor
Included
Input
Universal Sensor
Optional
Input
Mix
Demand
signal
Input
Boiler
Demand
signal
Input
Setpoint
or DHW
Demand
signal
Input
Remote Start/
Stop Module or
Remote Display
Module (RDM)
7
9
8
Input
Zone
Control
for boiler
zones
70
OR
OR
OR
OR
H1210B
Do not apply power
Vista de página 0
1 2 3 4 5 6 ... 35 36

Resumo do Conteúdo

Página 1 - - Data Brochure

- Data BrochureUniversal Reset Control 364D 36407/01 1 of 36 © 2001 D 364 - 07/01The Universal Reset Control 364 is designed to maximize the comf

Página 2 - Menu Item

© 2001 D 364 - 07/01 10 of 36 MIXING INDOOR (MIX INDR)The MIX INDR is the room temperature used in the original heat loss calculations for the bui

Página 3 - Status Field

11 of 36 © 2001 D 364 - 07/01EXTERNAL MIXING DEMANDAn external mixing demand allows for the use of a conventional thermostat system for zoning.

Página 4

© 2001 D 364 - 07/01 12 of 36 The Universal Reset Control 364 is capable of controlling a single zone snow melting system. In order to provide the

Página 5 - Section B2

13 of 36 © 2001 D 364 - 07/01RUNNING TIME (RUN TIME)The run time is the length of time the snow melting system operates once the slab has reache

Página 6 - Section C4

© 2001 D 364 - 07/01 14 of 36 In cases where a slab sensor has not been or cannot be installed in the snow melting slab, it is possible for the Un

Página 7 - Section C2: DHW PRIORITY

15 of 36 © 2001 D 364 - 07/01BOILER SENSOR ON THE SUPPLY (Boil SENS = SUP)The boiler sensor can be located on the boiler supply if the 364 is th

Página 8 - Outdoor Air Temperature

© 2001 D 364 - 07/01 16 of 36 BOILER OPERATIONWhen the 364 determines boiler operation is required, the Boiler contact terminals (15 and 16) close

Página 9 - Section D3

17 of 36 © 2001 D 364 - 07/01STEP THREE ————— ROUGH-IN WIRINGAll electrical wiring terminates in the control base wiring chamber. The base has s

Página 10 - Section D2: Mixing Devices

© 2001 D 364 - 07/01 18 of 36 DHW DemandTo generate a DHW demand, a voltage between 24 V (ac) and 240 V (ac) must be applied across the Setp / DHW

Página 11 - Section D3: Mixing Demands

19 of 36 © 2001 D 364 - 07/01 Sensor and Unpowered Input ConnectionsDo not apply power to these terminals as this will damage the control.Outdo

Página 12 - Section E4

© 2001 D 364 - 07/01 2 of 36 This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control S

Página 13 - Surface temperature = 35˚F

© 2001 D 364 - 07/01 20 of 36 DHW SensorA DHW Sensor 071 can connect to the DHW input. Connect the two wires from the sensor to the Com and DHW te

Página 14

21 of 36 © 2001 D 364 - 07/01 Test The OutputsPrimary Pump (Prim P1)If a primary pump is connected to the Prim P1 terminal (8), make sure that

Página 15 - Section F3

© 2001 D 364 - 07/01 22 of 36 Connecting The ControlMake sure all power to the devices and terminal blocks is off, and remove any remaining jump

Página 16 - ——————

23 of 36 © 2001 D 364 - 07/01The Universal Reset Control 364 comes with four Access Level settings. These Access Levels restrict the number of M

Página 17

© 2001 D 364 - 07/01 24 of 36 364 View Menu (1 of 2)Item FieldAccessLevelDescriptionRangeSectionLTDUSERINSTADV---, 35 to 100°F(2 to 38°C)D3-58 to

Página 18

25 of 36 © 2001 D 364 - 07/01364 View Menu (2 of 2)364 Adjust Menu (1 of 5)Item FieldAccessLevelDescriptionRangeActual SettingSectionLTDUSERINST

Página 19 - Zone Controltekmar 364

© 2001 D 364 - 07/01 26 of 36 364 Adjust Menu (2 of 5)Item FieldAccessLevelDescriptionRangeActual SettingSectionLTDUSERINSTADVOFF, -30 to 50°F(OFF

Página 20

27 of 36 © 2001 D 364 - 07/01Item FieldAccessLevelDescriptionRangeActual SettingSectionLTDUSERINSTADV364 Adjust Menu (3 of 5)-60 to 50°F(-51 to

Página 21 - Boil Sys

© 2001 D 364 - 07/01 28 of 36 Item FieldAccessLevelDescriptionRangeActual SettingSectionLTDUSERINSTADV364 Adjust Menu (4 of 5)LITE, MED, HEVYDefau

Página 22 - Cleaning

29 of 36 © 2001 D 364 - 07/01Item FieldAccessLevelDescriptionRangeActual SettingSectionLTDUSERINSTADV364 Adjust Menu (5 of 5)364 Misc (Miscellan

Página 23 - Access Levels

3 of 36 © 2001 D 364 - 07/01Symbol Description Display Mix DemandBoiler DemandDHW DemandSetpoint DemandWWSDMin / MaxMeltingButtonsSelects Menus,

Página 24

© 2001 D 364 - 07/01 30 of 36 The Universal Reset Control 364 has a built-in test routine which is used to test the main control functions. The 36

Página 25

31 of 36 © 2001 D 364 - 07/01When troubleshooting any heating system, it is a good idea to establish a set routine to follow. By following a con

Página 26

© 2001 D 364 - 07/01 32 of 36 Error DisplayedDescription of Error364 Error Messages (1 of 3)The control was unable to store a piece of information

Página 27

33 of 36 © 2001 D 364 - 07/01Error DisplayedDescription of Error364 Error Messages (2 of 3)The control is no longer able to read the mix return

Página 28

© 2001 D 364 - 07/01 34 of 36 Error DisplayedDescription of Error364 Error Messages (3 of 3)The control is no longer able to read the DHW sensor d

Página 29

35 of 36 © 2001 D 364 - 07/01Notes

Página 30 - Testing the Control

Product design, software and literature are Copyright © 2001 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.All specifications are sub

Página 31

© 2001 D 364 - 07/01 4 of 36 POWERING UP THE CONTROLWhen the Universal Reset Control 364 is powered up, the control displays the control type numb

Página 32 - 364 Error Messages (1 of 3)

5 of 36 © 2001 D 364 - 07/01The Universal Reset Control 364 is capable of providing a reset supply water temperature from the primary boiler loo

Página 33 - 364 Error Messages (2 of 3)

© 2001 D 364 - 07/01 6 of 36 WARM WEATHER SHUT DOWN (WWSD)When the outdoor air temperature rises above the WWSD setting, the 364 turns on the WWSD

Página 34 - 364 Error Messages (3 of 3)

7 of 36 © 2001 D 364 - 07/01Internal Demand (tekmar Sensor)If the DHW SENS item is set to DHW, the 364 looks for a DHW sensor connected to the D

Página 35

© 2001 D 364 - 07/01 8 of 36 Boiler and Mixing Priority (DHW PRI = B+M)It can be selected that the DHW tank has priority over the boiler and mixin

Página 36 - Technical Data

9 of 36 © 2001 D 364 - 07/01Once the boiler supply temperature is sufficiently reduced, the DHW device shuts off. Then the heating system is tur

Comentários a estes Manuais

Sem comentários