- Data Brochure
Zone Control 367
D 367
07/95
The Zone Control 367 is a microprocessor-based energy management control that uses PID
logic to control the temperature in up to 6 heating zones. Multiple zone controls can be daisy
chained together for up to 36 zones of heating. The 367 allows a variety of zoning options
including: single stage zones, two stage zones and modulating zones. The 367 is designed
to stagger zone operating times in order to minimize boiler short cycling and allow boiler
purging between cycles. The 367 has a built in night setback timer and a separate Optimum
Start / Stop feature for each zone. When the 367 is used with a tekmar reset control, the 367
provides indoor temperature feedback that adjusts the supply water temperature in order to
satisfy the zone with the highest heat load. Central ventilation, mechanical cooling and free
cooling systems can also be directly controlled through the 367.
Zone Control 367
One & Two Stage / One Stage & Floating
Power
Heat Required
Zone 2 / Hi stage /
Close / Ventilation
System Pump
24 hr. Timer
• Dial the desired duration
of the UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.
Start
UnOccupied
Duration
0 = always Occupied
24 = always UnOccupied
Zone 1 / Lo stage /
Open / Cooling
2
3
4
1
Zone 4 / Hi stage
Close
Zone 3 / Lo stage
Open
5
6
Zone 6 / Hi stage
Close
Zone 5 / Lo stage
Open
70°F
(21°C)
40
(4)
100
(38)
UnOccupied
Occupied
Optimum Start / Stop
UnOccupied
Timer Active
0
12 hrs.
24
618
Control Strategy . . . . . . . . . . . . . . . . pg. 2 Advanced Settings . . . pg. 13
Basic Sequence of Operation . . . . . pg. 3 Testing the Control . . .pg. 13
Basic Installation . . . . . . . . . . . . . . . pg. 6 Error Messages . . . . . . pg. 15
Basic Settings . . . . . . . . . . . . . . . . . . pg. 9 Technical Data . . . . . . . pg. 16
Advanced Sequence of Operation . . pg. 10 Limited Warranty . . . . . pg. 16
Advanced Installation . . . . . . . . . . . . pg. 12
Zone Control 367
One & Two Stage / One Stage & Floating
H1121 2
Made in Canada by
tekmar Control Systems Ltd.
N
123
Pmp
4
Power
L
11 12 13 14
Power
Pump Relay
Zone Relays
120 V 50/60 Hz 8 VA
120 V (ac) 10 A 1/3 hp, pilot duty 240 VA
120 V (ac) 6 A 1/3 hp, pilot duty 240 VA
Aug 95
31000266
24 2523 26 27
Do not apply power here
21 22
5-6
Com
70°F
(21°C)
40
(4)
100
(38)
UnOccupied
5678910
LR 58223
NRTL/C
R
Occupied
Optimum Start / Stop
UnOccupied
Timer Active
24 hr. Timer
0
12 hrs.
24
618
• Dial the desired duration of the
UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.
Start
15 16 17
Com
Sen
RTU
1
RTU
2
Com
Sen
RTU
3
RTU
4
Com
Sen
UnO
Sw
Zo
In
Com
Sen
Out
Sen
2018 19
5
Caution: Signal wiring must be rated at least 300V
UnOccupied
Duration
0 = always Occupied
24 = always UnOccupied
M
M
M
M
PRGM
S
TIME
AMPM
UNOCC
OVR
SMWTFT
1
2
LR 58233
E150539
70
70
70
70
Max. Room
40
65°F
Off
85
Floating Motor
Speed
130 sec.
30 230
100
200
0°F
-40 Off
Design Outdoor
30
Zone 1 Heating
One Stage & Floating
Off
Zone 1 Cooling
Optimum Start
Thermal Motor
Zone
Occ/UnOcc
Zone 2 Ventilating
Zone 2 Heating
1,2
43
Occ. only
56
One & Two Stage
Power
Heat Required
Zone 2 / Hi stage /
Close / Ventilation
System Pump
Zone 1 / Lo stage /
Open / Cooling
2
3
4
1
Zone 4 / Hi stage /
Close
Zone 3 / Lo stage /
Open
5
6
Zone 6 / Hi stage /
Close
Zone 5 / Lo stage /
Open
Pmp
System
Zo
Out
RTU
5
RTU
6
63-4
Com
341-2
Com
12
70
70
LR 58233
E150539
Test
M
M
Input
120 V (ac)
Power
Supply
Input
tekmar Zone
Control
Output
System
Pump
Input
Outdoor
Sensor
Input
tekmar RTUs or
Indoor Sensors
or
Ventilation
Outputs
Zone Valves or
Zone Pumps
Output
Cooling
Input
tekmar
Timer
Output
tekmar Reset
Control
Zone Valve or
Zone Pump
or
Vista de página 0
1 2 3 4 5 6 ... 15 16

Resumo do Conteúdo

Página 1 - - Data Brochure

- Data BrochureZone Control 367D 36707/95The Zone Control 367 is a microprocessor-based energy management control that uses PIDlogic to control the te

Página 2 - Control Strategy

10 Floating Motor Speed This dial has no effect on the operation of the control unless modulating zone valves areused. See the

Página 3 - Basic Sequence of Operation

11Common Blocks The 367 has 3 common blocks for both the RTU inputs and relay outputs. Each common block

Página 4 - Two Stage Common Blocks

12Advanced InstallationThis section supplements the basic installation that begins on page 6.Sensor and Unpowered Input Connections Do

Página 5 - 24 hr. Timer

13Floating Action Zones• If a floating action actuating motor is connected to the terminals Com 1-2 —1 —2 (19, 20 and 21), make sure power to the moto

Página 6 - Basic Installation

14Step 3 -The control tests relays 3 and 4 using the procedure described in Step 2.Step 4 -If the DIP switches are set to Zone 1 Heating and Zone 2

Página 7 - 

15STEP NINE BEFORE YOU LEAVE • Make sure the wiring safety dividers are installed in their proper locations between compartments with different volta

Página 8 - 19 20 21

16All specifications are subject to change without notice.Printed in Canada on recycled paper.In North America: tekmar Control Systems Ltd., Canadatek

Página 9 - Basic Settings

2Control StrategyZONING OPERATION In a multiple zone heating system, the zones may have different internal heat gains, heat losses or different tempe

Página 10 - DIP Switch Settings

3At the start of the night setback period the heat is turned off, but the heatcontained within the slab or radiator continues to heat the building and

Página 11 - Design Outdoor

4ZONING OPERATION The 367 can directly control the temperature of up to 6 One Stage heating zones or 3 TwoStage heating zones or a combination of One

Página 12 - Advanced Installation

5Fast Acting Zone Valves or Zone Pumps If the Thermal Motor DIP switch is set to Off, the 367 assumes that fast acting zone valvesor

Página 13 - Testing the Control Functions

6UnOccupied Temperature When the 367 is in UnOccupied mode, the UnOccupied light is turned on and theUnOccupied dial is used to

Página 14 - Manual Test

7be installed at a later time.Power must not be applied to any of the wires during the rough-in wiring stage.•Optional If an Outdoor Sensor 070 is use

Página 15 - Error Messages

8Sen — RTU 4 (8 and 10) terminals.Common block for RTU 1 and RTU 2DIP switch set to Zone 1 Heating• If the common block is used for a single One Stage

Página 16 - Technical Data

9Test the Sensors In order to test the sensors and Room Temperature Units (RTUs), the actual temperatureat each sensor and