- Data Brochure
Boiler Control 268
D 268
11/10
1 of 32 © 2010 D 268 - 11/10
The tekmar Boiler Control 268 can control the supply water temperature from up to 9 on / off stages based on outdoor temperature,
control for Domestic Hot Water (DHW) generation, a setpoint requirement or optionally an external input signal (0 - 10 V (dc)). A large
easy to read display provides current system temperatures and operating status. The control has outputs for a primary pump and
either a combustion air damper or alert. Based on the mode of operation selected, the control can operate different combinations of
boiler stages and boiler pumps.
Additional functions include:
DHW demand for DHW loads
Setpoint demand for setpoint loads
Test sequence to ensure proper component operation
CSA C US certified
Setback input for energy savings
0 - 10 V (dc) input signal
Input
Universal Sensor
Included
Input
Universal Sensor
Included
Input
Outdoor
Sensor
Included
Input
Timer or Switch
Optional
Input
Setpoint / DHW
Demand
Input
115 V (ac)
Power Supply
Input
Boiler
Demand
Output
Primary
Pump
Output
Combustion Air
Or Alert
Output
Boiler
Output
Pump
Or
Or
Output
Boiler
Output
DHW Pump Or
DHW Valve
Or
21
Com
Sup Ret Sw Dem Dem DHW N–+ LP1 1122334455667788
3
Boil Boil Out UnO Boil Com Setp/ Prim
4 5
6
7
8
9
10
11
12
13 14
15
16
17 18
19
20 21
22
23 24
25
26 2827
29
30 31
Boiler Control 268
Nine Stage Boiler & DHW / Setpoint
Do not apply power
Signal wiring must be rated at least 300 V.
H2026C
Alert DHW
C.A. /Power Relay Relay Relay Relay Relay Relay Relay Relay Relay 9/
Rotate
Alert
Off
Fixed Last
Off
Exercise
Adv
External Input
Stand Alone
Installer
C.A.
First On / Last Off
Fixed Lead
First On / First Off
Menu Item
Boiler Demand
DHW / Setpoint Demand
WWSD
External Input Signal
Offset
Modes
1 Up to 9 On/Off Boilers
2 Up to 4 On/Off Boilers & 4 Pumps
3
Up to 4 Lo/Hi Boilers
4 Up to 3 Lo/Hi Boilers & 3 Pumps
5 Up
to 3 Three Stage Boilers
6
Up to 2 Three Stage Boilers & 2 Pumps
7 Up to 2 Four Stage Boilers
8 1 Four Stage Boiler & 1
Pump
Test
off not testing
red testing
red testing paused
For
maximum
heat, press &
hold
Tes
t for 3
seconds.
943-01
Made in Canada by
tekmar Control Systems Ltd.
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp
Demands 20 to 260 V (ac) 2 VA
Date Code
CUS
Input
0-10 V (dc)
External Signal
Or
Meets Class B:
Canadian ICES
FCC Part 15
M
Priority Override
Installer and Advanced access levels
Primary pump output
Individual boiler pump outputs (in applicable modes)
• Pump exercising
Pump purging (primary and boiler)
Boiler demand for space heating loads
Note:
Boiler, DHW, or
setpoint demand
must be powered
with 20 to 260 V (ac)
before the boiler is
able to fire.
Vista de página 0
1 2 3 4 5 6 ... 31 32

Resumo do Conteúdo

Página 1 - - Data Brochure

- Data BrochureBoiler Control 268D 26811/10 1 of 32 © 2010 D 268 - 11/10The tekmar Boiler Control 268 can control the supply water temperature fro

Página 2

© 2010 D 268 - 11/10 10 of 32 CHARACTERIZED HEATING CURVEThe control varies the supply water temperature based on the outdoor air temperature. The

Página 3 - Menu Field

11 of 32 © 2010 D 268 - 11/10 High Mass Radiant (1)This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour.

Página 4 - (Stand Alone)

© 2010 D 268 - 11/10 12 of 32 Section E1DHWSection E: Domestic Hot Water Operation Section E1: Domestic Hot Water (DHW)DHW DEMANDA DHW Demand is re

Página 5 - (C. A.)

13 of 32 © 2010 D 268 - 11/10 CONDITIONAL DHW PRIORITYThe Conditional DHW Priority Override applies to DHW MODE 2 and 4. If the boiler supply te

Página 6 - Section B1

© 2010 D 268 - 11/10 14 of 32 DHW MODE 2 OPERATIONOn a call for DHW, the control provides DHW priority by shutting off the primary pump (Prim P1) f

Página 7

15 of 32 © 2010 D 268 - 11/10 Section F1SetpointSection F: Setpoint OperationSection F1: Setpoint7ComDem8Setp/DHW24 to 230 V (ac)Setpoint operat

Página 8 - Section C1

© 2010 D 268 - 11/10 16 of 32 Section G1External InputEXTERNAL INPUTThe control can accept an external DC signal in place of the outdoor sensor. Th

Página 9 - Section D1

17 of 32 © 2010 D 268 - 11/10 External Input Signal Conversion Tables CAUTIONImproper installation and operation of this control could result in

Página 10

© 2010 D 268 - 11/10 18 of 32 Power must not be applied to any of the wires during the rough-in wiring stage.• All wires are to be stripped to a l

Página 11

19 of 32 © 2010 D 268 - 11/10 Output ConnectionsPrimary Pump Contact (Prim P1)The Prim P1 output terminal (11) is a powered output. When the re

Página 12 - Section E1

© 2010 D 268 - 11/10 2 of 32 The control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to se

Página 13

© 2010 D 268 - 11/10 20 of 32 Setpoint DemandIf a setpoint demand is used, measure the voltage between the Setp / DHW and the Com Dem terminals (8

Página 14 - DHW MODE 4 OPERATION

21 of 32 © 2010 D 268 - 11/10 1234Com–BoilRetOut+BoilSup500Ω0 - 10 V (dc) 0 - 20 mAORV9PowerLNPrimP11011LN1312C.A./AlertM24 to 230 V (ac)LNOR151

Página 15 - Section F1

© 2010 D 268 - 11/10 22 of 32 The control’s exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping

Página 16 - Section G1

23 of 32 © 2010 D 268 - 11/10 Rotate / OffThe Rotate / Off DIP switch selects whether or not the control is to provide Equal Run Time Rotation o

Página 17 - ——————

© 2010 D 268 - 11/10 24 of 32 View Menu (1 of 2) Outdoor - Current outdoor air temperature as measured by the outdoor sensor.This item is only ava

Página 18 - Do Not Apply Power

25 of 32 © 2010 D 268 - 11/10 Adjust Menu (1 of 4)D1Room Occupied - The desired room air temperature during the occupied period.This item is onl

Página 19 - Relay 9/

© 2010 D 268 - 11/10 26 of 32 B1Boiler 2 - Selects whether or not boiler 2 is operational.This item is available in modes 1 to 7.Au (Auto), OFFDefa

Página 20 - 20 to 260 V (ac)

27 of 32 © 2010 D 268 - 11/10 Adjust Menu (3 of 4)ABoiler Minimum - The minimum allowed boiler target temperature.OFF, 80 to 180°F(OFF, 27 to 82

Página 21 - (C.A. / Alert)

© 2010 D 268 - 11/10 28 of 32 Adjust Menu (4 of 4)E1DHW Boilers Selects how many boilers are to be operated during DHW generation. (This item is on

Página 22 - Dip Switch Settings

29 of 32 © 2010 D 268 - 11/10 The control has a built-in test routine that is used to test the main control functions. The control continually m

Página 23 - Off / Exercise

3 of 32 © 2010 D 268 - 11/10 StageDisplays which stage relays are turned on.Primary PumpDisplays when the primary pump relay is turned on.Warnin

Página 24 - Advanced

© 2010 D 268 - 11/10 30 of 32 The control was unable to read a piece of information stored in its memory. Because of this, the control was required

Página 25

31 of 32 © 2010 D 268 - 11/10 Notes

Página 26 - Display Description Range

32 of 32Product design, software and literature are Copyright © 2010 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.All specificatio

Página 27 - Adjust Menu (3 of 4)

© 2010 D 268 - 11/10 4 of 32 Section AGeneralOperationPage 4 - 6Section BStagingPage 6 - 8Section CPumpOperationPage 8 - 9Section DBoiler Reset(Sta

Página 28 - Adjust Menu (4 of 4)

5 of 32 © 2010 D 268 - 11/10 SETBACK (UNOCCUPIED)To provide greater energy savings, the control has a setback feature. With setback, the supply

Página 29 - Testing the Control

© 2010 D 268 - 11/10 6 of 32 RUNNING TIMESThe control displays the accumulated running time of each boiler in the VIEW menu. When using a multi-sta

Página 30 - Error Messages

7 of 32 © 2010 D 268 - 11/10 LO / HI OR LO / LOWhen using multi-stage boilers, a selection must be made regarding the staging order of the boile

Página 31

© 2010 D 268 - 11/10 8 of 32 BOILER MASSThe BOIL MASS setting allows the installer to adjust the control to the thermal mass of the type of heat so

Página 32 - Technical Data