- Data Brochure
Boiler Control 270
D 270
08/10
1 of 24 © 2010 D 270 - 08/10
The tekmar Boiler Control 270 can control the supply water temperature from a single modulating boiler based on outdoor temperature
or domestic hot water requirements. A large easy to read display provides current system temperatures and operating status.
Additional functions include:
Input
Universal Sensor
Included
Input
Indoor Sensor
Optional
Input
Outdoor
Sensor
Included
Input
Boiler
Demand
Input
DHW
Demand
Output
Primary
Pump
Input
115 V (ac)
Power Supply
Output
DHW Pump or
DHW Valve
Output
Boiler
Output
Pump
OR
Input
tekmar
Timer
M
1
Boil
Dem
2
Com
Dem
3
DHW
Dem
Prim
P1
4 5
NL
6
Power
7 8 9 10 11
+--
12 13 14 15 16 17 18
Mod V(dc) Out Com Indr
UnO Boil
Com
Sw
Boiler Control 270
One Modulating Boiler & DHW
Boiler
Pmp P2
DHW
Pmp/Vlv
H2039A
Menu Item
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
Test
off not testing
red
testing
red
testing paused
Made in Canada by
tekmar Control Systems Ltd.
tektra 969-03
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
For maximum heat
press & hold Test
button for 3 second
s.
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
Advanced Off
Installer Exercise
Do not apply power
• Outdoor Reset
Installer and Advanced access levels
• Primary pump output
• Pump exercising
• Pump purging
Boiler demand for space heating loads
DHW demand for domestic hot water loads
Optional indoor sensor for room air temperature control
Test sequence to ensure proper component operation
Setback input for energy savings
CSA C US certified
Vista de página 0
1 2 3 4 5 6 ... 23 24

Resumo do Conteúdo

Página 1 - - Data Brochure

- Data BrochureBoiler Control 270D 27008/10 1 of 24 © 2010 D 270 - 08/10The tekmar Boiler Control 270 can control the supply water temperat

Página 2 - Table of Contents

© 2010 D 270 - 08/10 10 of 24 Fancoil (3)A fancoil terminal unit or Air Handling Unit (AHU) consists of a hydronic heating coil and either a

Página 3 - DHW Priority Override

11 of 24 © 2010 D 270 - 08/10DHW Mode 1 - DHW in Parallel no PriorityWhen a DHW Demand is present, the DHW Pmp / Vlv contact (terminals

Página 4 - Section E

© 2010 D 270 - 08/10 12 of 24 DHW MODE 2 OPERATIONOn a call for DHW, the control provides DHW priority by shutting off the primary pump (Pri

Página 5

13 of 24 © 2010 D 270 - 08/10DHW MODE 4 OPERATIONIn DHW MODE 4, the space heating zones must be prevented from coming on during DHW deman

Página 6 - 2 – 10 V (dc)

© 2010 D 270 - 08/10 14 of 24 56115 V (ac)LNPowerLN12BoilDemComDem24 to 230 V (ac)NL23ComDemDHWDem24 to 230 V (ac)NLL115 V (ac)NPrimP1PowerL

Página 7

15 of 24 © 2010 D 270 - 08/10Modulation OutputThe Modulation Output terminals (11 and 12) provide a 0 to 10 V (dc) or a 2 to 10 V (dc) ou

Página 8 - Section C: Pump Operation

© 2010 D 270 - 08/10 16 of 24 Test The Power SupplyMake sure exposed wires and bare terminals are not in contact with other wires or ground

Página 9

17 of 24 © 2010 D 270 - 08/10CONNECTING THE CONTROLMake sure all power to the devices and terminal blocks is off, and remove any remainin

Página 10 - 24 to 230 V (ac)

© 2010 D 270 - 08/10 18 of 24 View Menu (1 of 1)Outdoor Current outdoor air temperature as measured by the outdoor sensor.-76 to 149°F(-60 t

Página 11 - DHW PRIORITY OVERRIDE

19 of 24 © 2010 D 270 - 08/10Adjust Menu (1 of 2)Room Occupied The desired room air temperature during the occupied period. 35 to 100°F(2

Página 12 - DHW DURING UNOCCUPIED

© 2010 D 270 - 08/10 2 of 24 How To Use The Data BrochureUser InterfaceTable of ContentsDIP Switch Settings ...

Página 13

© 2010 D 270 - 08/10 20 of 24 Adjust Menu (2 of 2)DisplayDescriptionRangeSectionInstallerAdvancedActualSettingB3Boiler Modulation Selects ei

Página 14 - 115 V (ac)

21 of 24 © 2010 D 270 - 08/10The control has a built-in test routine that is used to test the main control functions. The control continu

Página 15 - ——————

© 2010 D 270 - 08/10 22 of 24 MAX HEATThe control has a function called Max Heat. In this mode, the control turns on and operates the system

Página 16

23 of 24 © 2010 D 270 - 08/10Error Messages (1 of 1)E01The control was unable to read a piece of information stored in its memory. Becaus

Página 17 - DIP Switches

Technical Data 24 of 24Product design, software and literature are Copyright © 2010 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.Al

Página 18 - Description

3 of 24 © 2010 D 270 - 08/10DisplaySymbol DescriptionBoiler DemandDHW DemandModulationDHW Priority OverrideMenu FieldDisplays thecurrent

Página 19 - Advanced

© 2010 D 270 - 08/10 4 of 24 Section AGeneralOperationPage 4 - 5Section BBoilerOperationPage 5 - 7Section CPumpOperation Page 8The following defi

Página 20

5 of 24 © 2010 D 270 - 08/10EXERCISINGThe control has a built-in exercising feature that is selected through the Exercise / Off DIP switc

Página 21 - Testing the Control

© 2010 D 270 - 08/10 6 of 24 The Motor Speed is the amount of time the boiler requires to go from 0% modulation to 100% modulation.Gas valve actu

Página 22 - MAX HEAT

7 of 24 © 2010 D 270 - 08/10To calculate the Maximum Modulation, use the following formula:For 0 to 10 V (dc):Maximum Modulation = 0 V (d

Página 23 - Error Messages (1 of 1)

© 2010 D 270 - 08/10 8 of 24 Section C: Pump OperationPRIMARY PUMP OPERATIONSection D: Boiler Reset OperationBOILER DEMANDA boiler demand is requ

Página 24 - Technical Data

9 of 24 © 2010 D 270 - 08/10BOIL MAXBOIL DSGNOUT DSGNROOM OCCROOM UNOCC210(99)190(88)170(77)150(66)130(54)110(43)90(32)70(2 50°F(10°C)-