Boiler Control 263
D 263
03/09
1 of 36 © 2009 D 263 - 03/09
The tekmar Boiler Control 263 can control the supply water temperature from a single modulating boiler or up to 2 on / off stages
based on outdoor temperature, domestic hot water requirements, or setpoint requirements. A large easy to read display provides
current system temperatures and operating status. The control has an internal setback timer, which can have 2 events per day on a
24 hour, 5-1-1 day or 7 day schedule.
Additional functions include:
• Outdoor Reset
Installer and Advanced access levels
Primary pump output
• Pump exercising
• Pump purging
Boiler demand for space heating loads
DHW demand for domestic hot water loads
Setpoint demand for setpoint loads
Optional indoor sensor for room air temperature control
Test sequence to ensure proper component operation
Internal setback timer for energy savings
Setback input for energy savings
CSA C US certified
Input
Universal
Sensor
Optional
Input
Indoor
Sensor
Optional
Input
Universal
Sensor
Included
Input
Outdoor
Sensor
Included
Input
Boiler
Demand
Input
DHW
Demand
Input
Setpoint
Demand
Output
Primary
Pump
Input
115 V (ac)
Power Supply
Output
DHW Pump or
DHW Valve
Output
Boiler
Output
Boiler
Output
Pump
Output
Boiler
OR OR
Output
tekmar
Timer
M
1 2 3
DHW
Dem
4
Com
Dem
5
Setp
Dem
Prim
P1
6 7
NL
8
Power
9 10 11 12
1
13
1
14 15
+
16
-
17 18 19 20 21 22 23
Com Com Boil Out
DHW Indr
UnO
Sw
Boiler Control 263
Two Stage / One Modulating Boiler, DHW & Setpoint
Relay Mod 1 mA
Boiler
Demand
Relay
2/P2
DHW
Pmp/Vlv
H2038B
Menu Item
Boiler Demand
DHW Demand
Setpoint Demand
Modulation
Priority Override
Test
off not testing
red
testing
red
testing paused
Made in Canada by
tekmar Control Systems Ltd.
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
For maximum
heat press &
hold Test for 3
seconds.
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
None
Advanced
Setback
Off
Soft Stop
Exercise
DHW Sensor
Off
Rotate
Installer
Modes
1 Two On/Off Stages
2 One Modulating Boiler and Pump
Do not apply power
Note:
Boiler, DHW, or
setpoint demand
must be powered
with 20 to 260 V (ac)
before the boiler is
able to fire.
Vista de página 0
1 2 3 4 5 6 ... 35 36

Resumo do Conteúdo

Página 1 - - Data Brochure

- Data BrochureBoiler Control 263D 26303/09 1 of 36 © 2009 D 263 - 03/09The tekmar Boiler Control 263 can control the supply water temperat

Página 2 - Menu Item

© 2009 D 263 - 03/09 10 of 36 DIFFERENTIALA modulating boiler must be operated with a differential while operating in low fire. The boiler d

Página 3 - Priority Override

11 of 36 © 2009 D 263 - 03/09Section C1: Pump OperationSection C: Pump OperationSection C1PumpOperationPRIMARY PUMP OPERATIONThe primary

Página 4

© 2009 D 263 - 03/09 12 of 36 Section D1BoilerResetSection D: Boiler Reset OperationSection D1: Boiler Reset OperationBOILER DEMANDA boiler

Página 5 - Timer Switch

13 of 36 © 2009 D 263 - 03/09TERMINAL UNITSThe control provides for a selection between six different terminal unit types: two types of r

Página 6 - Section B3

© 2009 D 263 - 03/09 14 of 36 Typical settings for the boost function vary between 30 minutes and two hours for buildings that have a fast r

Página 7 - 672 hours 720 hours

15 of 36 © 2009 D 263 - 03/09DHW MODE AND PRIORITY OPERATIONThe control has four different modes of DHW operation, which depends on the p

Página 8

© 2009 D 263 - 03/09 16 of 36 CONDITIONAL DHW PRIORITYThe Conditional DHW Priority Override applies to DHW MODE 2 and 4. If the boiler suppl

Página 9

17 of 36 © 2009 D 263 - 03/09Section F1: SetpointSection F1SetpointOperationSection F: Setpoint OperationFor correct operation, close att

Página 10

© 2009 D 263 - 03/09 18 of 36 SETPOINT PRIORITY OVERRIDEThe setpoint has a Priority Override while in SETP MODE 2. In order to prevent the b

Página 11 - Section C1

19 of 36 © 2009 D 263 - 03/09STEP FOUR ELECTRICAL CONNECTIONS TO THE CONTROLGeneralThe installer should test to confirm that no voltage

Página 12 - Section D1

© 2009 D 263 - 03/09 2 of 36 How To Use The Data BrochureUser InterfaceTable of ContentsDIP Switch Settings ...

Página 13

© 2009 D 263 - 03/09 20 of 36 Relay 1 ContactMode 1 - Two ON / OFF StagesThe Relay 1 terminals (11 and 12) are isolated outputs in the cont

Página 14 - Section E2

21 of 36 © 2009 D 263 - 03/09The 0 to 20 mA output can be converted to 0 to 10 V (dc) using an external 500 Ω resistor across the Modulat

Página 15

© 2009 D 263 - 03/09 22 of 36 UnOccupied SwitchIf an external timer (tekmar Timer 032) or switch is used, connect the two wires from the ext

Página 16

23 of 36 © 2009 D 263 - 03/09Setpoint DemandIf a setpoint demand is used, measure the voltage between the Setp Dem and the Com Dem termin

Página 17 - Section F1

© 2009 D 263 - 03/09 24 of 36 DHW Pump Or Valve (DHW Pmp / Vlv)If a DHW pump or DHW valve is connected to the DHW Pmp / Vlv terminals (9 and

Página 18

25 of 36 © 2009 D 263 - 03/09DIP Switch SettingsGENERALThe DIP switch settings on the control are very important and should be set to the

Página 19

© 2009 D 263 - 03/09 26 of 36 View Menu (1 of 1)Outdoor Current outdoor air temperature as measured by the outdoor sensor.-76 to 149°F(-60 t

Página 20 - 115 V (ac)

27 of 36 © 2009 D 263 - 03/09Adjust Menu (1 of 3)AMode Selects the control mode of operation.1 (2 on / off)2 (1 mod & pump)Default =

Página 21 - Mod 1 mA

© 2009 D 263 - 03/09 28 of 36 Adjust Menu (2 of 3)DisplayDescriptionRangeSectionInstallerAdvancedActualSettingB2B3Boiler Differential The te

Página 22 - ——————

29 of 36 © 2009 D 263 - 03/09Adjust Menu (3 of 3)DHW Exchange Unoccupied Selects whether or not a DHW d e m a n d w ill b e r e s po n d

Página 23

3 of 36 © 2009 D 263 - 03/09DisplaySymbol DescriptionBoiler DemandDHW DemandSetpoint DemandModulationPriority OverrideMenu FieldDisplays thecu

Página 24 - TEST THE MODULATING OUTPUT

© 2009 D 263 - 03/09 30 of 36 SETTING THE TIMEStep OnePress and release the Menu button until the TIME menu is reached.Step TwoPress the Ite

Página 25 - DIP Switches

31 of 36 © 2009 D 263 - 03/09Schedule Menu (1 of 1)SETTING THE SCHEDULEA schedule allows the timer to automatically change between two pr

Página 26 - Description

© 2009 D 263 - 03/09 32 of 36 The control has a built-in test routine that is used to test the main control functions. The control continual

Página 27 - Advanced

33 of 36 © 2009 D 263 - 03/09MAX HEATThe control has a function called Max Heat. In this mode, the control turns on and operates the syst

Página 28

© 2009 D 263 - 03/09 34 of 36 Error Messages (2 of 2)The control is no longer able to read the boiler supply sensor due to an open circuit.

Página 29

35 of 36 © 2009 D 263 - 03/09Notes

Página 30 - Time Menu (1 of 1)

Technical Data 36 of 36Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.Al

Página 31 - Schedule Menu (1 of 1)

© 2009 D 263 - 03/09 4 of 36 Section AGeneralOperationPage 4 - 5Section BBoilerOperationPage 6 - 10Section CPumpOperation Page 11Sequence of Oper

Página 32 - Testing the Control

5 of 36 © 2009 D 263 - 03/09TYPES OF DEMANDSThe control stages or modulates the boiler(s) to control supply water temperature to a hydronic sy

Página 33 - Error Messages (1 of 2)

© 2009 D 263 - 03/09 6 of 36 Section B: Boiler OperationSection B1BoilerOperationSection B2Mode 1Two StageOperationSection B3Mode 2Modulating Boi

Página 34 - Error Messages (2 of 2)

7 of 36 © 2009 D 263 - 03/09ROTATIONThe control’s Equal Run Time Rotation function is fixed at 48 hours. The firing order of the boilers chang

Página 35

© 2009 D 263 - 03/09 8 of 36 Auto DifferentialIf the Auto Differential is selected, the control automatically determines the best differential as

Página 36 - Control Systems

9 of 36 © 2009 D 263 - 03/09Example 1:A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10