DHW Control 257
The DHW Control 257 is used for dedicated domestic hot water systems. The control operates two on/off boilers, or one
two-stage boiler to maintain the DHW Target temperature at the DHW Sensor. The control can operate in Proportional (P)
mode, or Proportional, Integral, Derivative (PID) mode.
Additional functions include:
Boiler rotation
Cumulative boiler run time hours
P or PID staging modes of operation
CSA and UL certified for use in the USA and Canada
DHW Control 257
Two Stage
Item
Date Code
Power: 24 V ±10% 50/60 Hz 3 VA
Relays: 240 V (ac) 10 A 1/3 hp
tektra 906-11
Meets Class B:
Canadian ICES
FCC Part 15
Stage Mode Delay
Target DHW
DifferentialDHW
1234
CR
7
Com
Sen
8
DHW
Sen
No Power
Signal wiring
must be rated
at least 300V
Made in Canada
Power Heat 1
56
H3014B
Heat 2
Rotate
On
Off
Input
Universal Sensor
Included
Output
Boiler
Output
Boiler
Input
24 V (ac)
Power Supply
Vista de página 0
1 2 3 4 5 6 ... 11 12

Resumo do Conteúdo

Página 1 - - Data Brochure

1 of 12 © 2009 D 257 - 03/09D 25703/09- Data BrochureDHW Control 257The DHW Control 257 is used for dedicated domestic hot water systems. The c

Página 2 - Table of Contents

© 2009 D 257 - 03/09 10 of 12 Program Menu Item Field Range Description Actual SettingStage Mode DelayTarget DHWDifferentialDHW70 to 190°F(21 to 8

Página 3 - Stage Mode Delay

11 of 12 © 2009 D 257 - 03/09Field TestTo test the control, push and hold the up button for 3 seconds while in the default menu. While in

Página 4 - Sequence of Operation

tekmar Control Systems Ltd., Canadatekmar Control Systems, Inc., U.S.A.Head Office: 5100 Silver Star RoadVernon, B.C. Canada V1B 3K4(250) 545-7749 Fax

Página 5 - Rotation

© 2009 D 257 - 03/09 2 of 12 How to Use the Data BrochureThis brochure is organized into three main sections.They are: 1) Sequence of Operation,

Página 6 - Installation

3 of 12 © 2009 D 257 - 03/09▼POINTERDisplays the control operation as indicated by the text.HEAT RELAYDisplays when the HEAT 1 relay is closed

Página 7 - Test the Power Supply

© 2009 D 257 - 03/09 4 of 12 Sequence of OperationWhen the DHW Control 257 is powered up all LCD segments are displayed for 2 seconds followed by

Página 8 - Control Settings

5 of 12 © 2009 D 257 - 03/09This function rotates the firing sequence of the two boilers based on the accumulated running hours of each stage.

Página 9 - Default Menu

© 2009 D 257 - 03/09 6 of 12 Step Three — Rough-in WiringThe wiring terminates in the two wiring chambers on the control. Determine whether the l

Página 10 - Program Menu

7 of 12 © 2009 D 257 - 03/09Test the OutputsHeat 1 and Heat 2 Make sure power is off to the boiler circuits and connect the TT contacts on the

Página 11 - Error Messages

© 2009 D 257 - 03/09 8 of 12 DIP Switch SettingsOff | On - RotateThe Off | On – Rotate DIP switch is used to turn boiler rotation on or off. When

Página 12 - Technical Data

9 of 12 © 2009 D 257 - 03/09DEFAULT MENUDefault Menu Item Field Range DescriptionStage Mode DelayTarget DHWDifferentialDHW-60 to 255°F(-51 to 1

Comentários a estes Manuais

Sem comentários