Adjust Menu (2 of 2)
The time delay the control can expect between the
time the boiler contact closes, and the burner fires.
0:00 to 3:00 min.
(1 sec. increments)
B3
The maximum boiler target supply water
temperature.
120 to 225°F
(49 to 107°C)
B3
The minimum temperature allowed for the boiler
target temperature.
OFF, 80 to 180°F
(OFF, 27 to 82°C)
B3
Section
Advanced
Installer
Display Description Range
Actual
Setting
The design supply water temperature used in the
heat loss calculation for the heating system.
70 to 220°F
(21 to 104°C)
B3
The differential that the control is to use when it is
operating the boiler.
Ad, 2 to 42°F
(Ad, -17 to 6°C)
B3
The systems warm weather shut down during the
occupied (Day) period.
35 to 100°F, OFF
(2 to 38°C, OFF)
B3
The systems warm weather shut down during the
unoccupied (Night) period.
35 to 100°F, OFF
(2 to 38 °C, OFF)
B3
The units of measurement that all of the
temperatures are to be displayed in the control.
°F, °C
This item exits the ADJUST menu by pressing
either the or button.
ADJUST
ADJUST
°
F
ADJUST
WWSD
°
F
OCC
UN
ADJUST
WWSD
°
F
OCC
ADJUST
DIFF
BOIL
Fire Delay
min
ADJUST
ADJUST
BOIL
°
F
MIN
ADJUST
BOIL
°
F
MAX
ADJUST
DSGN
BOIL
°
F