262 Adjust Menu (3 of 4)
• • •
• • •
The DHW storage tank’s temperature during the
Occupied period.
DHW SENS = DHW
DHW THRU ≠ NONE
The DHW storage tank’s temperature during the
UnOccupied period.
DIP switch =
Setback
DHW SENS = DHW
DHW THRU ≠ NONE
OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
Default = 140°F (60°C)
OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
Default = 120°F (49°C)
Occ
UnOcc
•
Sets the differential for the DHW storage tank.
DHW SENS = DHW
MODE = —2—
1 to 42˚F
(1 to 23˚C)
Default = 6°F (3°C)
Actual
Setting
LTD
USER
INST
ADV
Range
Access
Level
DescriptionItem Field
C1
C1
C4
• •
• •
The minimum boiler supply temperature to the
DHW heat exchanger during the Occupied period.
DHW SENS = NONE
DHW THRU ≠ NONE
Selects whether or not DHW will be generated
during the UnOccupied period.
DIP switch =
Setback
DHW SENS = NONE
DHW THRU ≠ NONE
OFF, 100 to 220˚F
(OFF, 38 to 104˚C)
Default = 180°F (82°C)
OFF,
DHW XCHG
Occ
setting
Default = OFF
UnOcc
Occ
• •
• •
Enables or disables the DHW priority function
over the heating load.
DHW THRU = PUMP
MODE = —1—
The minimum boiler supply temperature when a
setpoint demand is present during the Occupied
period.
MODE = —1—
NONE, BOIL
Default = BOIL
OFF, 70 to 220˚F
(OFF, 21 to 104˚C)
Default = 180°F (82°C)
Occ
UnOcc
Selects whether or not a setpoint demand will be
responded to during the UnOccupied period.
DIP switch =
Setback
MODE = —1—
• •
OFF,
SETPOINT
Occ
setting
Default = OFF
• •
Selects whether or not the setpoint demand will
have priority over the heating system.
MODE = —1—
NONE, BOIL
Default = NONE
• • •
The system’s warm weather shut down during the
Occupied period.
MODE = —1—
35 to 100˚F, O F F
(2 to 38˚C, OFF)
Default = 70°F (21°C)
Occ
C1
C1
C2
D1
D1
D1
B1