© 2007 D 162 - 08/07 14 of 32
ADJUST Menu (6 of 6)
Mode Item Field Range Access Description
1
2
4
5
6
NONE, ZONE,
CTRL
Default = NONE
ADV
WWSD
SECTION R
Select the type of Warm Weather Shut Down
desired. When the outdoor temperature rises
above the WWSD, heating is disabled.
Note: This item is only available when the control
is connected to a tN4 system, an outdoor sensor
is connected to one of the devices in the tN4
system, and Mode of Operation is set to Heat.
1
2
4
5
6
40 to 100°F, OFF
(4.5 to 38.0°C,
OFF)
Default = 70°F
(21.0°C)
ADV
WWSD OCCUPIED SECTION R
Select the outdoor temperature at which the Warm
Weather Shut Down occurs for the occupied
period. Heating is disabled when the outdoor
temperature rises above the WWSD.
Note:
This item is only available when Mode
of Operation is set to Heat and WWSD is set
to Zone.
1
2
4
5
40 to 100°F, OFF
(4.5 to 38.0°C,
OFF)
Default = 62°F
(16.5°C)
ADV
WWSD UNOCCUPIED SECTION R
Select the outdoor temperature at which the Warm
Weather Shut Down occurs for the unoccupied
period. Heating is disabled when the outdoor
temperature rises above the WWSD.
Note:
This item is only available when the Mode
of Operation is set to Heat, WWSD is set to
Zone, and a programmable setback schedule
has been selected.
1
4
OFF, 30 to 100°F
(OFF, -1.0 to
38.0°C)
Default = OFF
ADV
CWSD OCCUPIED SECTION R
Select the outdoor temperature at which the Cold
Weather Shut Down occurs for the occupied
period. Cooling is disabled when the outdoor
temperature falls below the CWSD.
Note: This item is only available when the control
is connected to a tN4 system, an outdoor sensor
is connected to one of the devices in the tN4
system, and Mode of Operation is set to Cool.
1
4
OFF, 30 to 100°F
(OFF, -1.0 to
38.0°C)
Default = OFF
ADV
CWSD UNOCCUPIED
SECTION R
Select the outdoor temperature at which the Cold
Weather Shut Down occurs for the unoccupied
period. Cooling is disabled when the outdoor
temperature falls below the CWSD.
Note: This item is only available when the control
is connected to a tN4 system, an outdoor sensor
is connected to one of the devices in the tN4
system, Mode of Operation is set to Cool, and
a programmable setback schedule has been
selected.
ADJUST MENU
After the last item, the control returns to the first item in the menu.