7 of 32 © 2007 D 162 - 08/07
VIEW MENU
VIEW Menu (1 of 2)
Mode Item Field Range Access Description
1
2
4
5
0:01 to 24:00 hr
LTD
USEr
InST
ADV
OCCUPIED TIME SECTION B, E, I
Displays the amount of time left on the manual
override. The setpoint device operates at the
Occupied temperature and then reverts back
Scheduled temperature. Time counts down to
0:00 hours.
Cancel the override by pressing the Up and Down
buttons together at the same time or through the
user switch or gateway.
Note: This item is only available when a
programmable setback schedule or normally
unoccupied has been selected.
1
4
-31 to 266°F
(-35.0 to 130.0°C)
SEC
LTD
USEr
InST
ADV
SETPOINT SECTION A, D
Displays the measured setpoint sensor
temperature.
2
-31 to 266°F
(-35.0 to 130.0°C)
SEC
LTD
USEr
InST
ADV
HOT TUB SECTION B
Displays the measured hot tub temperature.
3
-31 to 266°F
(-35.0 to 130.0°C)
SEC
LTD
USEr
InST
ADV
DHW TANK SECTION C
Displays the measured indirect domestic hot
water tank temperature.
5
-31 to 266°F
(-35.0 to 130.0°C)
SEC
LTD
USEr
InST
ADV
FLOOR SECTION E
Displays the measured floor temperature.
6
-31 to 266°F
(-35.0 to 130.0°C)
SEC
LTD
USEr
InST
ADV
POOL SECTION F
Displays the measured pool temperature.
The VIEW menu items display the current operating
temperatures and status information of the system.
Continued on next page.
Display Menus